Plumbing Code Requirements

Concrete Basement

Show location of any new plumbing fixture such as bar sink(s), bathroom sinks, toilets, bathtubs, showers, hot water heater(s), floor drain(s) and other plumbing fixtures on the floor plans. Show location of plumbing chases. Show the location of new washer hose connection bibs and laundry standpipe in new laundry rooms/space.

All cleanouts, valves, shut-offs and mechanical joints shall be accessible. Minimum clearance in front of cleanouts shall be 18 inches on 3 inches and larger pipes, and 12 inches on smaller pipes. Concealed cleanouts shall be provided with access of sufficient size to permit removal of the cleanout plug and rodding of the system. Cleanout plugs shall not be concealed with any permanent finishing material. Fixtures having concealed tubular traps shall be provided with an access panel or unobstructed utility space 12 inches in the least dimension.

Showers: Hinged shower doors shall open outward. All glass which encloses a shower shall be safety glazed. Shower heads shall be water-conserving with a maximum flow rate of 2.5 gallons per minute. All shower control valves shall be anti-scald with a hot water limit of 120F.

Bathroom sinks: Shall have waste outlets not less than 1 inch in diameter. A strainer, pop-up stopper, crossbar or other device shall be provided to restrict the clear opening of the waste outlet. Faucets shall be water-conserving with a maximum flow rate of 2.2 gallons per minute at 60 psi.

Toilets: Shall be water-conserving low consumption at 1.6 gallons per flush and shall be provided with a flush tank or similar device designed and installed to supply water in sufficient quantity and flow to flush the contents of the fixture, to cleanse the fixture and refill the fixture trap.

Bathtubs: Shall have outlets and overflows at least 1 inches in diameter, and the waste outlet shall be equipped with an approved stopper. All bathtub control valves shall be anti-scald with a hot water limit of 120F.

Sinks: To be provided with waste outlets not less than 1 inches in diameter. A strainer, crossbar or other device shall be provided to restrict the clear opening of the waste outlet. Faucets shall be water-conserving with a maximum flow rate of 2.2 gallons per minute at 60 psi.

Laundry tubs: Each compartment of a laundry tub shall be provided with a waste outlet not less than 1 inches in diameter and a strainer or crossbar to restrict the clear opening of the waste outlet.

Clothes washers: The discharge of a clothes washer shall be through an air break.